Provide isolated power supply voltage to the two-wire smart transmitter connected to the dangerous site, and isolate and convert the (4-20) mA signal generated by the transmitter to the safe zone control system or other smart meters.
Product description

WP-8000-EX series detection terminal isolated safety barrier (HART) provides isolated power supply voltage for the two-wire smart transmitter connected to the dangerous site, and isolates and converts the (4-20) mA signal generated by the transmitter Then it is transmitted to the safe zone control system or other intelligent instruments.


   The product supports two-way communication with HART digital signals. Also compatible with non-smart transmitters.


   This isolated safety barrier requires independent power supply, electromagnetic isolation between the power supply-input circuit-output circuit.


◆ Features

  ● Connect to the on-site two-wire smart transmitter.

  ● Provide the transmitter with a distribution voltage ≥ 16V (power supply ≥ 22VDC).

  ● Isolate and transmit the transmitter (4~20) mA signal.

  ● HART signal two-way communication isolation transmission.

  ● (4~20) mA or (1~5) V signal output can be selected, or other required DC signals.

  ● Modular watch movement design, no need for zero and full scale adjustment.

  ● With working power indicator.

  ● Single channel, input loop overcurrent protection.

  ● Plug and unplug terminal blocks, DIN rail card installation.

● Power supply

   Power connection: independent terminal 13 -, 14 +, can be plugged and unplugged

   Power supply voltage: (20~30) VDC

  Current consumption: at 24VDC, <65mA

   Power indicator: power on, LED light on: green


Input circuit (Exia IIC dangerous area)

   input channel: terminal 1-, 2+ wiring (see terminal wiring diagram)

  Signal input: transmitter (4~20)mA; HART digital signal

  The power distribution voltage of the drive transmitter: ≥16V

   Input impedance: Built-in input sampling resistance 50Ω


● Output circuit (safe area)

   output channel: terminal 11 -, 12 + wiring (see terminal wiring diagram)

   Output current: (4~20) mA, HART digital signal

   Allowable load during current output: 0~350Ω

   ripple (Vp-p): <10mV


● Performance Index

  Standard accuracy: ±0.5%FS, ±0.2%FS

   Temperature drift: ±0.015%/℃

   Response time: ≤1s (10→90)%

   Stable time: ≤3s

   Influence of power supply voltage fluctuation: ±0.1% (allowable voltage range)

   Influence of load resistance change: ±0.1%/250Ω

   Channel isolation: isolation between input-output-power supply

  Insulation resistance: ≥100MΩ/500VDC (AC)

   Isolation capacity: 2500VAC/1 minute 50Hz

   Maximum explosion-proof voltage: 250VAC

  Anti-electromagnetic compatibility: in line with IEC 61000 related anti-electromagnetic standards


● Environmental parameters

  Working temperature: (-20~+60)℃

  Storage temperature: (-40~+80)℃

  Environmental humidity: (5~+95)%RH (no condensation)


Structure

   Structure: card-mounted; modular watch core; ABS material case; plug-in terminal

   Machine weight: about 110g


● Safety and explosion-proof certification parameters

  The whole machine meets the GB3836.1-2000 and GB3836.4-2000 standards

   Standard related requirements

  Explosion-proof grade mark: [Exia]IIC

  Safety certification parameters:

     Um: 250V Uo: 28V Io: 93mA

    Po: 0.65W Lo: 2.4 mH Co: 0.03μF

 
Scan the QR code to read on your phone
We could not find any corresponding parameters, please add them to the properties table

Related Products

Smart differential pressure flowmeter is a smart flowmeter based on battery-powered low-power Internet of Things technology. It is mainly used for the detection of large-diameter water flow in urban water affairs and municipal pipe networks. It uploads collected water flow data and other information to the cloud server through a wireless remote
There are numerous municipal fire hydrants, scattered installations, destruction of fire hydrants, embezzlement of fire-fighting water, insufficient pressure of fire-fighting pipelines, and other problems. As a result,
WP304D temperature collector adopts MEMS temperature sensor chip to be encapsulated in a specific case. The temperature sensor and the conversion circuit are integrated to form a small special temperature sensor. Its appearance is small and exquisite, the measurement accuracy is high, the reliability is good, the power consumption is low,

Messages

Username used for comment:
Messages
Description:
验证码

CONTACT

Fujian WIDE PLUS Precision Instrument Co., Ltd.
National unified technical service telephone:
ADD:No.16, Xingye West Road, Mawei High-tech Zone,Fuzhou,Fujian China 350015

FOLLOW US

Copyright © Fujian WIDE PLUS Precision Instrument Co., Ltd. Powered by www.300.cn 闽ICP备05035149号-1